Breaker Capacity Calculator

Load current × safety factor → smallest KS-standard rating that satisfies the requirement. Includes inverter+ELB nuisance-trip warning.

Load Information

Result

Enter load current and type, then click Calculate.

Breaker Rating by Load Current (Korean KS Standard)

The most-searched values in one table. Each cell multiplies the load current by the load-type safety factor, then picks the smallest rating at or above it from the KS standard ratings below — MCB (63A and below) first, MCCB only if no MCB fits.

Load currentGeneral (×1.25)Motor direct-on-line (×1.5)Motor Y-Δ (×2.0)
5 A10 A10 A10 A
10 A16 A16 A20 A
15 A20 A25 A32 A
20 A25 A32 A40 A
25 A32 A40 A50 A
30 A40 A50 A63 A
40 A50 A63 A100 A
50 A63 A75 A100 A
60 A75 A100 A125 A
75 A100 A125 A150 A
100 A125 A150 A200 A
125 A175 A200 A250 A
150 A200 A225 A300 A
200 A250 A300 A400 A

KS Standard Ratings (A)

MCB (miniature, up to 63A)
6 · 10 · 16 · 20 · 25 · 32 · 40 · 50 · 63
MCCB (molded case)
15 · 20 · 30 · 40 · 50 · 60 · 75 · 100 · 125 · 150 · 175 · 200 · 225 · 250 · 300 · 350 · 400 · 500 · 600 · 800 · 1000 · 1200 · 1600 · 2000

These are first-pass selections based on safety factor alone. Actual design must also stay within the cable ampacity and coordinate with upstream breakers (selectivity) and starting characteristics. Use the calculator above to check margin and warnings.

Related rules (KEC = Korean Electrical Code): KEC 212.4.1 (overload protection conditions) · KEC 212.3.4 (characteristics of protective devices) · safety factors are this calculator's defaults, not KEC values

What this tool does

The breaker sizing calculator multiplies the load current by a load-type safety factor (this calculator's default, not a KEC value) to get the minimum rating, then picks the smallest rating at or above it from the MCB list (63A and below) first, and from the MCCB list only if no MCB fits. You can choose general, motor (direct-on-line, Y-Δ), inverter and welder loads, and it shows the calculation steps, safety margin and warnings. Put simply, the breaker rating must be at least the load current and no more than what the cable can carry (its ampacity) — check the second condition (KEC 212.4.1) with the wire size calculator. Useful for panel design, rating checks before quoting, and electrical license exam study.

Who uses this

  • Residential / commercial panel design: select breaker for each branch circuit
  • Motor load: first-pass rating from the default factor for each starting method (direct-on-line, Y-Δ) — check the breaker's instantaneous trip characteristic against starting current
  • Inverter / VVVF: see the leakage-trip warning when an ELB is used on the same circuit
  • Electrical quotes: check candidate ratings before pricing breakers
  • Electrical license exams: study the KEC overload protection conditions (212.4.1) — load-type safety factors are not KEC values

How to use (4 steps)

  1. 1Enter the load current (A). If you only know kW, convert it first with the power conversion calculator.
  2. 2Choose the load type: general lighting/outlets, motor direct start, motor Y-Δ start, inverter load, or welder. Each has a different default safety factor.
  3. 3Optionally enter your own safety factor, and tick the ELB box if an earth-leakage breaker is on the circuit. An inverter load with ELB ticked shows a leakage-trip warning.
  4. 4Click Calculate to see the recommended breaker (rating and MCB/MCCB), the MCCB-list rating when an MCB is chosen, applied safety factor, minimum required rating, safety margin, warnings, and calculation steps.

Breaker rating — calculation order and the KEC 212.4.1 conditions

KEC 212.4.1 overload protection conditions: Design current I_B (this calculator's 'load current') ≤ breaker rating I_n ≤ cable ampacity I_Z I_2 ≤ 1.45 × I_Z (I_2: the current that reliably trips the breaker within the conventional time — check the maker's data or the product standard; this calculator does not cover it) This calculator's steps: Minimum rating = load current × safety factor (load-type default — not a KEC value) → smallest rating at or above it from the MCB list (63A and below) first, then the MCCB list Example: general load 12A → 12 × 1.25 = 15A → 16A MCB Check yourself: chosen rating ≤ cable ampacity (I_n ≤ I_Z) → wire size calculator 3-phase load current (motor efficiency not included — including it gives a higher current): I = P / (√3 × V × power factor) Example: 7.5kW 380V PF 0.85 → 7,500 / (1.732 × 380 × 0.85) = 13.4A

Real examples

Example 1: Residential panel — living room lights + outlets (12A general)

12A × 1.25 = 15A → the smallest value at or above 15A in the MCB list is a 16A MCB (for 63A and below this calculator checks the MCB list first). Household panels must use residential circuit breakers (KEC 212.3.4), and the current this circuit's cable can carry (its corrected ampacity) must be at least 16A (KEC 212.4.1).

Example 2: 3-phase 380V 7.5kW motor

Current = 7,500 / (√3 × 380 × 0.85) = 13.4A (efficiency not included — nameplate kW is shaft output, so the actual supply current is higher; enter the efficiency in the power conversion calculator). Multiplying by the direct-on-line default safety factor of 1.5 gives 13.4 × 1.5 = 20.1A → 25A MCB (30A MCCB if you pick from the MCCB list). Treat 25A as a starting point: if you choose 25A, the cable ampacity must also be at least 25A (212.4.1). For low-voltage indoor motor circuits, KEC only requires the protective device to be chosen with the starting current of the starting method in mind; it sets no sizing multiplier (212.6.3 ②). Check that the inrush does not trip the breaker using the instantaneous trip curve (B, C, D for residential circuit breakers, Table 212.3-3) or the maker's characteristic curve. This MCB protects the wiring; indoor motors over 0.2kW also need their own overload protection, such as a thermal overload relay (212.6.3 ③, with exceptions).

Example 3: Inverter load — handling leakage trips

The rating is sized the same way as a general load (load current × inverter default safety factor 1.25). In inverter circuits, high-frequency leakage current can make a standard ELB trip unnecessarily. Even so, on circuits that require an ELB (KEC 211.2.3 ④, 211.2.4, etc.) do not remove it — check the ELB type (Type F or B, IEC 62423) and rated residual operating current recommended by the inverter maker.

Frequently asked questions

What's the difference between MCB, MCCB, and ELB?

In this calculator, MCB means a miniature circuit breaker (list 6~63A) and MCCB a molded-case circuit breaker (list 15~2000A); for 63A and below it picks an MCB first. These names split ratings by range and are not the same as KEC's industrial/residential classes — KEC sets trip characteristics separately for industrial and residential circuit breakers and requires residential ones where ordinary people may touch them, such as household panels (212.3.4). Check with the maker whether a product is a residential type. An ELB (earth-leakage breaker) mainly detects leakage current to prevent electric shock and leakage faults; some also provide overcurrent protection, and in TN systems an ELB used for fault protection must be a combined overcurrent type (211.2.5). Where ELBs are required starts with KEC 211.2.4, and separate clauses add places such as general-use outlets of 20A or less (211.2.3 ④) and bathroom outlets (234.5).

Why a 1.25 safety factor?

It is not a KEC value — it is this calculator's default for general loads. KEC 212.4.1 requires two conditions, not a multiplier: design current ≤ breaker rating ≤ cable ampacity, and the current that ensures operation ≤ 1.45 × cable ampacity. For a different margin, enter it in Custom Safety Factor.

Why are motor loads calculated differently?

This calculator sets the default safety factor for motor loads at 1.5 for direct-on-line and 2.0 for Y-Δ starting, higher than general loads (1.25). These are the calculator's defaults, not KEC values, so check them against the motor nameplate and the maker's starting-current data. For protective devices installed indoors on low-voltage circuits, KEC sets no multiplier; it requires the rating to be chosen with the starting current of the starting method in mind (212.6.3 ②). To check for trips during starting, compare the breaker's instantaneous trip curve (for residential circuit breakers: B over 3In up to 5In, C over 5In up to 10In, D over 10In up to 20In — Table 212.3-3; In is the breaker's rated current) with the motor's actual starting current.

How do I choose ELB sensitivity?

General-use outlets rated 20A or less used by ordinary people, and outdoor portable equipment rated 32A or less, must have additional protection by an ELB with a rated residual operating current of 30mA or less (211.2.3 ④, 211.6.1). An ELB alone is not accepted as a protective measure; it is additional protection used together with one of the measures in 211.2 to 211.5 (211.6.1). Outlets in bathrooms or toilets with a bathtub or shower, where people use electricity while wet, must be protected by a shock-protection ELB of 15mA or less with an operating time of 0.03s or less, an outlet with such an ELB built in, or an isolating transformer of 3kVA or less (234.5). Set other sensitivities by the clause for the installation location and the maker's data. This calculator sizes overcurrent ratings only.

Can I pick a non-standard rating?

If the calculated value falls between ratings, pick the next rating up (e.g. 20.1A → 25A). The calculator rounds up to the smallest rating at or above the minimum required rating, checking the MCB list (63A and below) first and then the MCCB list. When it picks an MCB, it also shows the same value rounded up within the MCCB list — use that one for panels that use MCCBs (e.g. 20.1A → 25A MCB · 30A MCCB). Available ratings and trip characteristics vary by maker, so confirm with the catalog. Going one rating down cuts the margin and can cause nuisance trips.

How do I match breaker rating with wire size?

Under KEC 212.4.1 the breaker rating must not exceed the cable ampacity (I_n ≤ I_Z). Ampacity is corrected for installation method, ambient temperature, and grouping, so size alone does not decide it. Use this site's wire size calculator to get the corrected ampacity and compare it with the chosen rating. This site's wire size calculator uses installation method B1 and corrects only for ambient temperature and grouping (number of circuits), so for other installation methods check the matching ampacity table directly.

ELBs keep tripping on inverter loads — why?

Inverters create high-frequency leakage current that can make a standard ELB trip unnecessarily. Even so, on circuits that require an ELB (KEC 211.2.3 ④, 211.2.4, etc.) do not remove it — check the ELB type (Type F or B, IEC 62423) and rated residual operating current recommended by the inverter maker. On such circuits, an ELB may be omitted only where a clause allows it — for example, supply through an isolating transformer with a secondary voltage of 300V or less and an unearthed load-side circuit (211.2.4 ① item 가, exception (5)), or circuits such as emergency lighting, whose interruption would affect public safety, with a ground-fault alarm to a monitoring station (211.2.4 ②).

Cautions

  • •This calculator picks a first-pass rating by multiplying the load current by a safety factor. Special loads such as UPS units and SMPS need separate review. For welders it sets only a first-pass rating with the intermittent-load default, so the breaker size recommended in the welder's specification comes first.
  • •The safety factors are this calculator's defaults, not KEC values. Whatever factor you use, the chosen rating must not exceed the cable ampacity (KEC 212.4.1).
  • •Values between standard ratings are rounded up to the next rating. Going one rating down cuts the margin and can cause nuisance trips.
  • •ELB sensitivity (30mA, 15mA, etc.) is set separately by the KEC clause for the installation location (211.2.3 ④, 234.5, etc.) and the maker's data. This tool sizes overcurrent ratings only.
  • •Final breaker selection should be reviewed by a qualified electrical engineer against KEC and site conditions; this calculator's results are for reference only.

Last reviewed: 2026-10-02

Materials for this result

This page contains Coupang Partners affiliate links, and we receive a commission on qualifying purchases.