Stair Calculator
This calculator turns total rise and preferred riser height into step count, riser and tread, and checks them against Article 16(1) of Korea's Regulations on Housing Construction Standards and the Blondel formula.
Result
Enter total rise and preferred riser height.
What this tool does
The stair calculator computes step count, actual riser height, tread depth, stair length, angle, and Blondel value from total rise (floor-to-floor height) and preferred riser. Riser and tread are compared with Article 16(1) of Korea's Regulations on Housing Construction Standards, which apply to housing built under an approved housing construction project plan, such as apartment complexes. “Shared” uses the values for stairs used in common (riser ≤ 180 mm, tread ≥ 260 mm), and “Residential” uses the values for outdoor stairs (riser ≤ 200 mm, tread ≥ 240 mm). The Regulations give no figures for indoor stairs in detached houses or inside an apartment unit, so “Residential” uses the less strict of these two sets of values as a reference. The tool also compares the result with the Blondel formula for comfortable walking (2R + T = 600–640 mm, where R = riser and T = tread) and flags results outside that range. Providing the optional total run enables measured tread instead of the Blondel-recommended default.
Who uses this
- New timber-frame homes: draft stair layout (step count, riser, tread) once floor-to-floor height is fixed
- Renovation: re-plan stair division when the floor-to-floor height changes
- Compact housing / loft stairs: in limited horizontal space, check riser and tread against the reference values and the Blondel range (2R + T), and read off the pitch angle
- Before preparing permit drawings: check whether riser and tread fall outside the reference values from Korea's housing construction standards
- Deck and exterior stairs: calculate slope angle and stringer length for outdoor construction
How to Use (4 Steps)
- 1Enter total rise in mm — the height from one finished floor surface to the next, finish materials included. Example: 2,700 mm between level 1 and level 2.
- 2Enter preferred riser height. Residential stairs typically target 170–180 mm. The tool rounds to the nearest whole step count and divides evenly.
- 3(Optional) Enter total run if you know the horizontal stair footprint. Leave blank to get the Blondel-formula tread recommendation (T = 620 − 2R).
- 4Choose the use type: “Shared” for stairs used in common (e.g. in an apartment complex), “Residential” for stairs in a detached house or inside an apartment unit. The thresholds change accordingly. Review the Blondel pass/fail indicator and any riser or tread warnings in the results.
Formulas & Standards
Step count = round(total rise ÷ preferred riser) [min 2] Actual riser (R) = total rise ÷ step count Tread depth (T): With total run → T = total run ÷ (step count − 1) Without total run → T = 620 − 2 × R (Blondel recommendation) Stair length = √(total rise² + (T × (step count − 1))²) Pitch angle = atan(R ÷ T) [degrees] Blondel value = 2R + T → 600–640 mm is the comfortable walking range Regulations on Housing Construction Standards, Article 16(1) (housing complexes under an approved housing construction project plan): Stairs used in common: R ≤ 180 mm, T ≥ 260 mm → this tool's “Shared” Outdoor stairs of a building: R ≤ 200 mm, T ≥ 240 mm → reference values for “Residential” (This provision sets no riser/tread values for indoor stairs in detached houses or inside an apartment unit) Stair headroom ≥ 2,100 mm — buildings over 200 m² total floor area (Enforcement Decree of the Building Act, Article 48(1) → Rules on Standards for Evacuation and Fire-Protection Structures of Buildings, Article 15(1)4)
Examples
Example 1: Total rise 2,700 mm, preferred riser 175 mm
Step count = round(2700 ÷ 175) = 15. Actual R = 2700 ÷ 15 = 180 mm. T = 620 − 2×180 = 260 mm (Blondel). Blondel = 2×180 + 260 = 620 mm → pass. Angle = atan(180÷260) = 34.7°. Stair length = √(2700² + (260×14)²) ≈ 4,532 mm.
Example 2: Total rise 3,000 mm, total run 3,640 mm
Preferred R 180 mm → step count = round(3000÷180) = 17. Actual R = 3000÷17 ≈ 176.5 mm. T = 3640÷(17−1) = 227.5 mm. Blondel = 2×176.5 + 227.5 = 580.5 mm → below 600 mm warning. Reduce step count or widen run to fix.
Example 3: Loft stair, total rise 2,000 mm, preferred riser 175 mm (checked against the stricter “Shared” values)
A loft stair in a detached house would normally use “Residential”, which gives no warning for this input. To show how the warnings work, it is checked here against the stricter “Shared” values (R ≤ 180 mm, T ≥ 260 mm). round(2000÷175) = 11 steps. R = 2000÷11 ≈ 181.8 mm → warning: over 180 mm. T = 620−2×181.8 ≈ 256.4 mm → warning: under 260 mm. Lowering the preferred riser to 170 mm gives round(2000÷170) = 12 steps: R ≈ 166.7 mm, T = 620−2×(2000÷12) ≈ 286.7 mm → both limits met. Angle = atan(166.7÷286.7) ≈ 30.2°.
Frequently asked questions
What is the Blondel formula?
The Blondel formula (2R + T = 600–640 mm) was proposed by 17th-century French architect François Blondel to describe the ergonomic stride length on stairs. When this range is satisfied, climbing feels natural without overstretching or shuffling. This calculator uses 620 mm as the target and warns when the value falls outside 600–640 mm.
Why does the actual riser differ from the preferred value I entered?
The tool rounds total rise ÷ preferred riser to the nearest integer to ensure every step is equal height. The actual riser (total rise ÷ rounded step count) will therefore differ slightly from your preferred value. Always verify the displayed 'actual riser' before drafting construction drawings.
Why is the tread auto-calculated when I leave total run blank?
Without a measured run, the Blondel formula T = 620 − 2R provides a recommended starting tread depth. This is useful in early design when only the floor-to-floor height is known. Enter the actual total run once the stair footprint is fixed to get precise tread dimensions.
Where are Korea's legal stair riser and tread limits?
This tool's “Shared” mode warns when the riser exceeds 180 mm or the tread is shallower than 260 mm, and “Residential” mode when the riser exceeds 200 mm or the tread is shallower than 240 mm. (1) Both sets of values come from Article 16(1) of Korea's Regulations on Housing Construction Standards, which apply to housing built under an approved housing construction project plan, such as apartment complexes: ‘stairs used in common’ need R ≤ 180 mm / T ≥ 260 mm, and ‘outdoor stairs of a building’ R ≤ 200 mm / T ≥ 240 mm (R = riser, T = tread). (2) Stairs in buildings over 200 m² total floor area follow Korea's Rules on Standards for Evacuation and Fire-Protection Structures of Buildings under Article 48(1) of the Enforcement Decree of the Building Act. Article 15(2) of those Rules sets riser and tread limits only for elementary schools (riser ≤ 160 mm, tread ≥ 260 mm) and middle and high schools (≤ 180 mm, ≥ 260 mm). (3) Neither regulation sets riser or tread limits for indoor stairs in detached houses or inside an apartment unit, so “Residential” uses the less strict of the two Article 16(1) sets of values, those for outdoor stairs, as a reference. Always verify current local authority requirements before permit submission.
How do I design stair width (clear width)?
This calculator does not compute stair width (the clear width between the two sides). The legal minimum depends on the building type and size. (1) Housing built under an approved housing construction project plan, such as apartment complexes: stairs used in common need a clear width of at least 120 cm, and outdoor stairs of a building at least 90 cm (Regulations on Housing Construction Standards, Article 16(1)). (2) Indoor stairs in buildings over 200 m² total floor area (the sum of all floor areas): under Article 15(2) of the Rules on Standards for Evacuation and Fire-Protection Structures of Buildings, at least 150 cm for elementary, middle and high schools, and at least 120 cm for performance halls, assembly halls, spectator venues, sales facilities and similar uses. In buildings other than the schools and performance, assembly, spectator and sales facilities above, stairs on an above-ground floor also need at least 120 cm if the habitable rooms (rooms used for living, work, assembly and the like) from the floor directly above that floor up to the top floor (or, if one of those upper floors is an evacuation floor, up to the floor below it) total 200 m² or more. Stairs on a basement floor whose habitable rooms total 100 m² or more also need at least 120 cm; all other stairs need at least 60 cm. Direct stairs that a quasi-high-rise building installs under the proviso to Article 34(4) of the Enforcement Decree of the Building Act are governed separately by Article 15(7) of the same Rules (at least 120 cm in apartment buildings, at least 150 cm in other buildings). (3) In buildings over 200 m² total floor area, railings (a wall or equivalent also counts) are required on both sides of stairs and landings (the flat resting areas between flights) more than 1 m high (same Rules, Article 15(1)2). (4) In housing complexes, railings must in principle be at least 120 cm above the finished floor, or at least 90 cm in lower-risk places such as stairs inside a building (Regulations on Housing Construction Standards, Article 18(2)1).
Can this calculator be used for outdoor stairs?
The geometry formulas apply equally to indoor and outdoor stairs, but outdoor stairs benefit from wider treads (to shed rainwater) and anti-slip finishes. In regions with winter icing, lowering risers to 150 mm or below is sometimes recommended.
Cautions
- •This tool uses the riser and tread values in Article 16(1) of the Regulations on Housing Construction Standards as reference values and flags results outside them. For actual design and permits, consult a licensed architect and confirm the latest requirements with the local authority.
- •Stair width (clear width), stair headroom (≥ 2,100 mm in buildings over 200 m² total floor area), and railings are not calculated here.
- •Total rise must reflect finished-floor-to-finished-floor height, including floor finish and stair tread thickness. Structural shell height will differ.
- •Step count is determined by rounding, so actual riser may differ from the preferred value. Use the displayed actual riser for all drawings.
- •Cutting a stair opening through floor joists requires double headers and trimmer/rim joists — consult a structural engineer.